Product description
- 0.1...20 m/s
0...200,000 m³/h - Temperature, flow velocity, volume flow
- Modbus RTU
- IP 65, sensors IP 20
- Installation length: 220 mm
Calibratable duct air flow sensor RHEASGARD® KLGF - Modbus with Modbus plug, housing made of impact-resistant plastic with quick-locking screws, with cable gland (optional M12 plug to DIN EN 61076-2-101) optionally with / without display, for determining the flow velocity (0.1...20 m/s). Calibratable duct air flow sensor RHEASGARD® KLGFVT - Modbus with Modbus plug, housing made of impact-resistant plastic with quick-locking screws, with cable gland (optional M12 plug to DIN EN 61076-2-101), optionally with/without display, for determining the flow velocity (0.1...20 m/s) and temperature (0...50 °C).
The flow sensors are suitable for monitoring or controlling air flows in ducts, on fans and dampers, for flow-dependent monitoring of humidifiers and electric heating registers in accordance with DIN 57100, section 420, or for use in conjunction with a heating register. 420, or for use in conjunction with DDC systems. Innovative Modbus sensor with electrically isolated RS485 Modbus interface, selectable bus terminating resistor, DIP switch for setting the bus parameters and bus address in de-energized state, internal LEDs for telegram status display, two separate push-in terminals and large three-line display (illuminated; with customer-specific programming in 7-segment and dot-matrix range). The sensor is calibrated at the factory.